Most of what people know about vacant-building rules comes from city registration ordinances. The fire code has its own, and it applies wherever the code has been adopted, registration or not. International Fire Code Section 311, Vacant Premises, covers securing, fire protection systems, combustible debris, hazardous materials and the placards that warn firefighters before they go in. The code is copyrighted, so this page summarizes it; the full text is free to read in the ICC's read-only view.
What Section 311 Requires
- 311.1 General: temporarily unoccupied buildings, structures, premises or portions, including tenant spaces, must be safeguarded and maintained under Sections 311.1.1 through 311.6
- 311.2.1 Security: exterior and interior openings accessible to other tenants or unauthorized persons must be boarded, locked, blocked or otherwise protected, and the fire code official may placard, post signs or tape off the premises
- 311.2.2 Fire protection: fire protection systems must be maintained in an operable condition at all times, subject to the exceptions below
- 311.2.3 Fire separation: fire-rated partitions, fire barriers and fire walls separating vacant tenant spaces must be maintained
- 311.3 Removal of combustibles: the person owning or in charge of the vacant building must remove accumulations of combustible materials, flammable or combustible waste and rubbish, and secure the openings, with exceptions for buildings under permitted work and seasonally occupied buildings
- 311.4 Removal of hazardous materials: owners of a vacant building containing hazardous materials must follow the facility closure requirements of Section 5001.6
- 311.6 Unoccupied tenant spaces in mall buildings: kept free of stored materials and combustible waste, separated by gypsum board, and kept broom-swept
The Sprinkler Exceptions
Section 311.2.2 is where vacant buildings get into trouble, because a sprinkler system in an unheated building can freeze. The section allows three exceptions, summarized: premises cleared of all combustibles and debris where the fire code official finds the construction, separation and security create no fire hazard; with the official's approval, unheated buildings exposed to freezing that have no contents and are secured, which may take fire alarm and sprinkler systems out of service and keep standpipes dry; and, with approval, seasonally occupied unheated buildings under 12,000 square feet that do not store vehicles or hazardous materials. Each depends on the official, so draining a sprinkler system in a vacant building is a conversation with the fire department first, not a maintenance decision. The water side of that is covered in fire watch and vacant building requirements.
When a Vacant Building Becomes Abandoned
Section 311.1.1 says a building is considered abandoned, declared unsafe and abated by demolition or rehabilitation under the property maintenance and building codes when, in summary, the owner cannot be identified or located by a certificate of mailing to the last known or registered address; it repeatedly becomes unprotected or unsecured; it has been occupied by unauthorized persons or for illegal purposes; or it presents a danger of collapse or fire spread to adjacent properties. Three of those four are about security, which is why a building that stays locked and checked rarely reaches this section.
The Placards
- Unsafe vacant or abandoned buildings are marked under Sections 311.5.1 to 311.5.5
- Location: the front of the structure, visible from the street, with more beside each entrance
- Size and color: at least 24 by 24 inches, red background, white reflective stripes and border
- Date: the date applied and the date of the most recent inspection
- Symbols: a plain square for normal structural conditions when marked; one diagonal for structural or interior hazards, enter with extreme caution; an X for consider exterior-only operations; letters above it for hazards such as roof open, stairs missing, avoid fire escapes, holes in floor
- The symbols are informational and do not limit the incident commander
How the States We Cover Adopt It
| State | Statewide fire code | Section 311 |
|---|---|---|
| Ohio | Ohio Fire Code, OAC 1301:7-7, IFC 2021 base, effective November 20, 2025 | Adopted with Ohio's 311.2.1.1 for vacant and abandoned foreclosure property: secure under R.C. 2308.031, no plywood, quick-release devices where made |
| Oklahoma | IFC 2024, OAC 748:20-4, effective September 14, 2026 | Not modified; applies as published |
| Alabama | IFC 2021, State Fire Marshal rule 482-2-101-.02, effective January 1, 2025 | Not excepted; applies where the state rule governs |
| Arkansas | 2021 Arkansas Fire Prevention Code (IFC 2021 with state rules), effective January 1, 2023 | No Section 311 amendment found |
| Louisiana | R.S. 40:1578.7 adopts NFPA 1 or the IFC as the state uniform fire prevention code | We did not confirm which edition the fire marshal enforces |
| Pennsylvania | The Uniform Construction Code uses the IFC only to the extent other ICC codes reference it | No statewide Section 311; local adoptions such as Philadelphia's apply |
| Texas | No statewide fire code; cities adopt and amend the IFC | Varies by city |
Ohio's Plywood Rule
Ohio is the one state we cover that adds to Section 311. Its Section 311.2.1.1 says residential property subject to the expedited foreclosure of vacant and abandoned property under R.C. 2308.02 must be secured in accordance with R.C. 2308.031, and that if a quick-release device is manufactured for the product used to secure the property, it must be installed. R.C. 2308.031, in force since April 6, 2017, says no person shall use plywood to secure real property deemed vacant and abandoned under R.C. 2308.02. For an Ohio foreclosure board-up under R.C. 2308.02, the securing product has to be something other than plywood.
What Compliance Looks Like on a Visit
- Every exterior opening checked and secured, with dated photographs of each door and window
- Fire protection system status recorded: sprinkler valve positions, alarm panel condition, and any approved out-of-service arrangement in writing
- Combustible debris, trash and rubbish removed, and the interior photographed clear
- Any placard in place photographed, and the fire department notified if the building's condition has changed
- Signs of entry or occupation reported the same day, since repeated unsecured status is one of the abandonment triggers
Ethreon secures and maintains vacant commercial and residential buildings with its own local crews across the seven states it covers: openings secured, using non-plywood products on Ohio foreclosure properties, debris removed, fire system status recorded, and every visit closed with dated photographs. See board-up, securing vacant commercial buildings, vacant property checks, or check coverage.
Send Your ScopeRelated Services
Ethreon delivers these services with full documentation and compliance reporting:
Frequently Asked Questions
1What does the fire code require for a vacant building?
International Fire Code Section 311 requires temporarily unoccupied buildings, structures, premises or portions of them to be safeguarded and maintained under Sections 311.1.1 through 311.6. In summary: openings must be boarded, locked, blocked or otherwise protected against unauthorized entry; fire protection systems must be kept operable, subject to listed exceptions; and accumulations of combustible materials, waste and rubbish must be removed.
2Do sprinklers have to stay on in a vacant building?
IFC Section 311.2.2 requires fire protection systems to be maintained in an operable condition at all times, with three exceptions in summary: premises cleared of combustibles where the fire code official finds no fire hazard; with approval, unheated buildings exposed to freezing that have no contents and are secured, which may take alarm and sprinkler systems out of service and keep standpipes dry; and, with approval, certain seasonally occupied unheated buildings.
3When is a building considered abandoned under the fire code?
IFC Section 311.1.1 treats a building as abandoned, unsafe and subject to abatement by demolition or rehabilitation when, in summary, the owner cannot be located by certificate of mailing, it repeatedly becomes unsecured, it has been occupied by unauthorized persons or for illegal purposes, or it presents a danger of collapse or fire spread to adjacent property.
4What do the red placards on vacant buildings mean?
IFC Section 311.5 requires unsafe vacant buildings to be marked with placards at least 24 by 24 inches, red with white reflective stripes. A plain square means normal structural conditions when marked; a square with one diagonal means structural or interior hazards and interior operations with extreme caution; a square with an X means firefighters should consider exterior-only operations. Letters above the symbol flag hazards such as an open roof or holes in the floor.
5Can I read the International Fire Code for free?
Yes, in a read-only view. The International Code Council offers free, read-only access to a selection of its codes at codes.iccsafe.org, including the International Fire Code and the International Property Maintenance Code, without an account; the free view does not allow copying, pasting or printing.
6Does Ohio add anything to IFC 311?
Yes. The Ohio Fire Code, Ohio Administrative Code 1301:7-7-03, effective November 20, 2025, adds Section 311.2.1.1: residential property subject to Ohio's expedited foreclosure of vacant and abandoned property under R.C. 2308.02 must be secured under R.C. 2308.031, which prohibits plywood, and a quick-release device must be installed if one is made for the product used.