Home/Blog/REO & Compliance
REO & Compliance8 min read

The Fire Code's Rules for Vacant Buildings: IFC Section 311 and How Each State Adopts It

The International Fire Code has a section written for vacant buildings. Section 311 requires temporarily unoccupied premises to be secured against entry, fire protection systems kept operable, combustibles and rubbish removed, and unsafe vacant buildings marked with standard placards for firefighters. It also defines when a building is considered abandoned. Ohio, Oklahoma, Alabama and Arkansas adopt it statewide; Ohio adds its own rule for foreclosure properties. The code is free to read online.

Most of what people know about vacant-building rules comes from city registration ordinances. The fire code has its own, and it applies wherever the code has been adopted, registration or not. International Fire Code Section 311, Vacant Premises, covers securing, fire protection systems, combustible debris, hazardous materials and the placards that warn firefighters before they go in. The code is copyrighted, so this page summarizes it; the full text is free to read in the ICC's read-only view.

What Section 311 Requires

  • 311.1 General: temporarily unoccupied buildings, structures, premises or portions, including tenant spaces, must be safeguarded and maintained under Sections 311.1.1 through 311.6
  • 311.2.1 Security: exterior and interior openings accessible to other tenants or unauthorized persons must be boarded, locked, blocked or otherwise protected, and the fire code official may placard, post signs or tape off the premises
  • 311.2.2 Fire protection: fire protection systems must be maintained in an operable condition at all times, subject to the exceptions below
  • 311.2.3 Fire separation: fire-rated partitions, fire barriers and fire walls separating vacant tenant spaces must be maintained
  • 311.3 Removal of combustibles: the person owning or in charge of the vacant building must remove accumulations of combustible materials, flammable or combustible waste and rubbish, and secure the openings, with exceptions for buildings under permitted work and seasonally occupied buildings
  • 311.4 Removal of hazardous materials: owners of a vacant building containing hazardous materials must follow the facility closure requirements of Section 5001.6
  • 311.6 Unoccupied tenant spaces in mall buildings: kept free of stored materials and combustible waste, separated by gypsum board, and kept broom-swept

The Sprinkler Exceptions

Section 311.2.2 is where vacant buildings get into trouble, because a sprinkler system in an unheated building can freeze. The section allows three exceptions, summarized: premises cleared of all combustibles and debris where the fire code official finds the construction, separation and security create no fire hazard; with the official's approval, unheated buildings exposed to freezing that have no contents and are secured, which may take fire alarm and sprinkler systems out of service and keep standpipes dry; and, with approval, seasonally occupied unheated buildings under 12,000 square feet that do not store vehicles or hazardous materials. Each depends on the official, so draining a sprinkler system in a vacant building is a conversation with the fire department first, not a maintenance decision. The water side of that is covered in fire watch and vacant building requirements.

When a Vacant Building Becomes Abandoned

Section 311.1.1 says a building is considered abandoned, declared unsafe and abated by demolition or rehabilitation under the property maintenance and building codes when, in summary, the owner cannot be identified or located by a certificate of mailing to the last known or registered address; it repeatedly becomes unprotected or unsecured; it has been occupied by unauthorized persons or for illegal purposes; or it presents a danger of collapse or fire spread to adjacent properties. Three of those four are about security, which is why a building that stays locked and checked rarely reaches this section.

The Placards

  • Unsafe vacant or abandoned buildings are marked under Sections 311.5.1 to 311.5.5
  • Location: the front of the structure, visible from the street, with more beside each entrance
  • Size and color: at least 24 by 24 inches, red background, white reflective stripes and border
  • Date: the date applied and the date of the most recent inspection
  • Symbols: a plain square for normal structural conditions when marked; one diagonal for structural or interior hazards, enter with extreme caution; an X for consider exterior-only operations; letters above it for hazards such as roof open, stairs missing, avoid fire escapes, holes in floor
  • The symbols are informational and do not limit the incident commander

How the States We Cover Adopt It

Statewide adoption of the International Fire Code, and Section 311, as of November 18, 2026
StateStatewide fire codeSection 311
OhioOhio Fire Code, OAC 1301:7-7, IFC 2021 base, effective November 20, 2025Adopted with Ohio's 311.2.1.1 for vacant and abandoned foreclosure property: secure under R.C. 2308.031, no plywood, quick-release devices where made
OklahomaIFC 2024, OAC 748:20-4, effective September 14, 2026Not modified; applies as published
AlabamaIFC 2021, State Fire Marshal rule 482-2-101-.02, effective January 1, 2025Not excepted; applies where the state rule governs
Arkansas2021 Arkansas Fire Prevention Code (IFC 2021 with state rules), effective January 1, 2023No Section 311 amendment found
LouisianaR.S. 40:1578.7 adopts NFPA 1 or the IFC as the state uniform fire prevention codeWe did not confirm which edition the fire marshal enforces
PennsylvaniaThe Uniform Construction Code uses the IFC only to the extent other ICC codes reference itNo statewide Section 311; local adoptions such as Philadelphia's apply
TexasNo statewide fire code; cities adopt and amend the IFCVaries by city

Ohio's Plywood Rule

Ohio is the one state we cover that adds to Section 311. Its Section 311.2.1.1 says residential property subject to the expedited foreclosure of vacant and abandoned property under R.C. 2308.02 must be secured in accordance with R.C. 2308.031, and that if a quick-release device is manufactured for the product used to secure the property, it must be installed. R.C. 2308.031, in force since April 6, 2017, says no person shall use plywood to secure real property deemed vacant and abandoned under R.C. 2308.02. For an Ohio foreclosure board-up under R.C. 2308.02, the securing product has to be something other than plywood.

What Compliance Looks Like on a Visit

  • Every exterior opening checked and secured, with dated photographs of each door and window
  • Fire protection system status recorded: sprinkler valve positions, alarm panel condition, and any approved out-of-service arrangement in writing
  • Combustible debris, trash and rubbish removed, and the interior photographed clear
  • Any placard in place photographed, and the fire department notified if the building's condition has changed
  • Signs of entry or occupation reported the same day, since repeated unsecured status is one of the abandonment triggers

Ethreon secures and maintains vacant commercial and residential buildings with its own local crews across the seven states it covers: openings secured, using non-plywood products on Ohio foreclosure properties, debris removed, fire system status recorded, and every visit closed with dated photographs. See board-up, securing vacant commercial buildings, vacant property checks, or check coverage.

Send Your Scope

Frequently Asked Questions

1What does the fire code require for a vacant building?

International Fire Code Section 311 requires temporarily unoccupied buildings, structures, premises or portions of them to be safeguarded and maintained under Sections 311.1.1 through 311.6. In summary: openings must be boarded, locked, blocked or otherwise protected against unauthorized entry; fire protection systems must be kept operable, subject to listed exceptions; and accumulations of combustible materials, waste and rubbish must be removed.

2Do sprinklers have to stay on in a vacant building?

IFC Section 311.2.2 requires fire protection systems to be maintained in an operable condition at all times, with three exceptions in summary: premises cleared of combustibles where the fire code official finds no fire hazard; with approval, unheated buildings exposed to freezing that have no contents and are secured, which may take alarm and sprinkler systems out of service and keep standpipes dry; and, with approval, certain seasonally occupied unheated buildings.

3When is a building considered abandoned under the fire code?

IFC Section 311.1.1 treats a building as abandoned, unsafe and subject to abatement by demolition or rehabilitation when, in summary, the owner cannot be located by certificate of mailing, it repeatedly becomes unsecured, it has been occupied by unauthorized persons or for illegal purposes, or it presents a danger of collapse or fire spread to adjacent property.

4What do the red placards on vacant buildings mean?

IFC Section 311.5 requires unsafe vacant buildings to be marked with placards at least 24 by 24 inches, red with white reflective stripes. A plain square means normal structural conditions when marked; a square with one diagonal means structural or interior hazards and interior operations with extreme caution; a square with an X means firefighters should consider exterior-only operations. Letters above the symbol flag hazards such as an open roof or holes in the floor.

5Can I read the International Fire Code for free?

Yes, in a read-only view. The International Code Council offers free, read-only access to a selection of its codes at codes.iccsafe.org, including the International Fire Code and the International Property Maintenance Code, without an account; the free view does not allow copying, pasting or printing.

6Does Ohio add anything to IFC 311?

Yes. The Ohio Fire Code, Ohio Administrative Code 1301:7-7-03, effective November 20, 2025, adds Section 311.2.1.1: residential property subject to Ohio's expedited foreclosure of vacant and abandoned property under R.C. 2308.02 must be secured under R.C. 2308.031, which prohibits plywood, and a quick-release device must be installed if one is made for the product used.

Keep Reading

More guides for property teams.

REO & Compliance

FHA Property Preservation Requirements: What Servicers Must Know

Grass to a maximum of two inches. Utilities off by default, with six exceptions. Snow cleared after a three-inch accumulation. Shrubs once a season between April 1 and October 31. The FHA standards are more specific than most summaries of them, and this page gives them as the handbook states them.

REO & Compliance

When a Home in the Community Is Abandoned: What an HOA Board Can Legally Do in Texas, Ohio, Pennsylvania and Louisiana

An abandoned house in a subdivision is the board's problem long before it is the bank's: overgrown yards, open doors, complaints from neighbors. But the statutes give associations far less power to step onto a lot than most boards assume. Texas gives no statutory right to enter or mow and requires notice and a cure period before fines; Ohio allows entry only for imminent risk of harm; Pennsylvania and Louisiana require owners to allow access reasonably needed for upkeep. What each state allows, and the route that works.

REO & Compliance

Louisiana Blighted Property: Act 456 of 2025, Hearing-Officer Condemnation, and Expropriation in East Baton Rouge

Louisiana's Act 456 of 2025, Senate Bill 236, effective August 1, 2025, lets any parish or municipality empower its administrative hearing officer to condemn blighted or abandoned property and authorize demolition, makes the hearing officer decide condemnations in Baton Rouge and East Baton Rouge, and extends the fast expropriation-by-declaration-of-taking procedure, already used by New Orleans and Grambling, to East Baton Rouge Parish and its municipalities. Act 382 of 2026 then widened the ordinance scope statewide. What an owner of a vacant property should know.